Sudden oil pressure relay

Protective relay (relay) for detecting internal faults in transformers.

 This relay is attached with the top or side of an oil-immersed transformer,and at the designed to detect an abnormal pressure rise in the tank close the contacts when an accident inside the transformer.

Type: SSPO-2LLB/SSPO-3C

Catalogue (PDF)


Type SSPO-2LLB SSPO-3C
Minimum operating pressure difference 25kPa±15% 31kPa±15%
Minimum rate of operating pressure rise 2.0kPa/s±25% 2.9kPa/s±25%
Kinds of contact Normally-open contact
Insulation resistance More than 100MΩ by 500V megger
Withstand Voltage Between electric circuit and the case, AC2000V
Ambient Temperature -30~80℃